Sign In | Join Free | My uabig.com
China Sansion Power Electric Co., Ltd. logo
Sansion Power Electric Co., Ltd.
Providing One-Stop Service For Customers
Active Member

8 Years

Home > Impulse Voltage Test System >

High Voltage Impulse Voltage Test System , 200 KV / 10 KJ Impulse Generator

Sansion Power Electric Co., Ltd.
Contact Now

High Voltage Impulse Voltage Test System , 200 KV / 10 KJ Impulse Generator

  • 1
  • 2

Brand Name : Sansion

Model Number : SXCF

Certification : ISO, SGS, CE, ilac-MRA, CNAS

Place of Origin : Wuhan, China

MOQ : 1 set

Price : Negotiation

Payment Terms : T/T, L/C, Western Union

Supply Ability : 100 sets per year

Delivery Time : 15-35 working days

Packaging Details : Plywood Cases

Nominal Voltage : 200kV or at Customized

Rated Energy : 10kJ or at Customized

Impulse Capacitance : 0.5UF or at Customized

Each Stage : 100kv 0.25UF or at Customized

Standard : IEC

Display : LCD

Contact Now

200kV / 10kJ High Voltage Impulse Voltage Test System For Lighting Test

System instruction Main Parameters for System

1. Nominal voltage: ±200kV

2. Rated stage voltage: ±100kV

3. Rated energy: 10kJ

4. Impulse capacitance: 0.5µF

5. Number of stages: 2

Rated stage capacitance: 1µF(each impulse capacitor 1µF at 100kV, total 2pcs)

Impulse voltage waveform: generated when load capacitance is 300-3000pF.

T1=1.2µs±30%, T2=50µs±20%, standard lightning impulse voltage full waveform of peak voltage deviation≤3%;


Standard operation waveform 250±20%/2500±60%. These 2 Impulse voltage waveform parameters and error are accorded with national requirements of IEC standard.

1. Voltage utilization factor: Standard lightning impulse voltage waveform ≥90% when load capacitance is below 1000pF, standard operation impulse voltage waveform≥80% when load capacitance is below 2000pF.

2. Standard operation impulse voltage waveform ≥70%.​

3. Locking range: level voltage is within the range of 20%-100% rated voltage, positive and negative locking range no less than 25%.

4. Out-of-control rate of synchronous discharge: <5%

5. Min. output voltage: ≥±20% of rated voltage.

6. Instability of discharge voltage: <±1.0%

7. Continuous time: Above 2/3 of rated voltage, continuous working when charge and discharge once every 120s. Below 2/3 of rated voltage, continuous working when charge and discharge once every 60s.


More details please contact Sansion Power by email for further information.


Product Tags:

high voltage impulse generator

      

impulse voltage generator

      